Concept Direct (UK) Ltd 2008
For air temperatures, use the ARH4 or the AAV3. When it is not practical to touch
the test point (e.g. A ceiling vent) use the ATIR3 infrared head. Infrered is not
recommended for pipe temperatures. For comparing temperatures ( two temperatures
at once) use the ATH4 with the K-Type thermocouple with the small industry standard
plugs.
Two K-Type thermocouple inputs. Display T1,T2 or T1-T2.
- +ºF accuracy after simple field calibration.
- Range: -50ºF to 1500ºF (optional hi-temp thermocouple required).
- Displays ºF directly at 0.1ºF resolution on DMM with 0.1mVDC resolution.
- Select ºF or ºC.
- Includes two “wrap tab” thermocouples plus velcro straps. Thermocouples insulated
to 400ºF.
- Auto off can be disabled for data logging (DL3).
Use for quick temperature measurements.
- Measures temperature without contact.
- 8: Field of view
- Laser sight included.
- Select ºF or ºC.
- Operating ambient temperature: 32ºF to 122ºF at <75%RH.
- Range: 0ºF to 752ºF.
- Accuracy: Whichever is greater. At 73ºF + 10ºF at <90%RH; + 2.0%rdg or 4ºF, 32ºF
to 160ºF; + 3.0%rdg or 5.5ºF, 0ºF to 31ºF, 161ºF to 752ºF.
Measures air temperature and RH%. Displays wet bulb for getting target superheat
from manufacturers charts.
- + 1ºF, 32ºF-113ºF.
- + 2.5% RH, 10% to 90% RH @ 77ºF.
- Select ºF or ºC.
- Displays temperature, RH%, wet bulb and dew point.
- Auto off can be disabled for data logging (DL3).
Measures air velocity. Use to estimate CFM. Also displays temperature.
- Max operating temperature: 120ºF.
- Use with DL3 to find average air flow and compute CFM.
Air Velocity.
- Ft/min, M/s, MPH, KM/hr.
- Range: 80 5900 ft./min
- Accuracy: + 3% + 1dgt.
Temperature.
- Displays ºF or ºC.
- Range: -4ºF to 140ºF.
- Accuracy: + 1ºF from 32ºF to 113ºF.
- Resolution: 0.5ºF.